Model including all safety levels
Aggregation of the four main safety controls of a refrigerant
machine (heat pump or chiller).
The order is based on the relevance to a real system. Antifreeze
control and mininmum flow rate control are put last because of the
relevance for the simulation. If the medium temperature falls below
or rises above the critical values, the simulation will fail.
All used functions are optional. See the used models for more
information on each safety function:
- May 27, 2025 by Fabian Wuellhorst:
Make safety checks parallel (see issue IBPSA
#2015)
- May 26, 2025 by Fabian Wuellhorst and Michael
Wetter:
Increase error counter only when device should turn on (see issue
IBPSA
#2011)
- October 2, 2022 by Fabian Wuellhorst:
Adjusted based on the discussion in this issue #1576)
- November 26, 2018 by Fabian Wuellhorst:
First implementation (see issue AixLib
#577)