This model describes boundary conditions for pressure, enthalpy, and species concentration that can be obtained from weather data.
To use this model, connect weather data from
IDEAS.BoundaryConditions.WeatherData.ReaderTMY3 to the port
weaBus
of this model.
This will cause the medium of this model to be
at the pressure that is obtained from the weather file, and any flow that
leaves this model to be at the temperature and humidity that are obtained
from the weather data.
If the parameter use_C_in
is false
(default option),
the C
parameter
is used as the trace substance for flow that leaves the component, and the
C_in
input connector is disabled; if use_C_in
is true
,
then the C
parameter is ignored, and the value provided by the input connector is used instead.
Note that boundary temperature, mass fractions and trace substances have only an effect if the mass flow is from the boundary into the port. If mass is flowing from the port into the boundary, the boundary definitions, with exception of boundary pressure, do not have an effect.