.IDEAS.Fluid.Storage.Examples.StratifiedUnloadAtMinimumTemperature

Information

Example for tank model that has three outlets, each with a valve. The valve at the bottom opens when the temperature in that tank segment is sufficiently warm to serve the load. The tank in the middle also opens when its tank temperature is sufficiently high, but only if the valve below is closed. Finally, the valve at the top only opens if no other valve is open. Hence, there is always exactly one valve open. On the right-hand side of the model is a heater that adds heat to the bottom of the tank if the top tank segment is below the set point temperature.

Contents

NameDescription
 MediumMedium model

Revisions


Generated at 2024-12-04T19:25:49Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos