modelTrafoRect
Extends from Icons.TrafoRect.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.ApparentPower | S_rT | 2.8*1e6 | Transformer: Rated power |
| Modelica.Units.SI.Voltage | V_rTs | 372.09 | Transformer: Rated secondary side voltage |
| Modelica.Units.SI.Power | P_rTLoss | 2800 | Transformer: Power losses at rated operation |
| Types.Percent | V_sc | 7 | Transformer: Short-circuit voltage |
| Modelica.Units.SI.Frequency | f_nom | 50 | Grid: nominal frequency |
| Modelica.Units.SI.Inductance | L_dc | 0.001 | Inductance on DC side |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| Interfaces.VoltageInput | v_dc | ||
| PowerSystems.Generic.Ports.Terminal_n | terminal_ac | AC connection | |
| PowerSystems.AC1ph_DC.Ports.TwoPin_n | terminal_dc | DC connection |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.Current | i_dc | Current through electrolyzer | |
| Modelica.Units.SI.Angle | alpha | Firing angle | |
| Modelica.Units.SI.Angle | delta | Sum of firing and overlap/commutation angle | |
| Modelica.Units.SI.Angle | mu | delta - alpha | Overlap/commutation angle |
| Modelica.Units.SI.Power | P | Real power drawn from Grid | |
| Modelica.Units.SI.ReactivePower | Q | Reactive power drawn from Grid | |
| Modelica.Units.SI.AngularFrequency | omega | 2*pi*f_nom | Grid: angular frequency |
| Modelica.Units.SI.Current | I_rTs | Transformer: Rated secondary side current | |
| Modelica.Units.SI.Impedance | Z_T | Transformer impedance, absolute value | |
| Modelica.Units.SI.Angle | Phi_ZT | Angle of transformer impedance | |
| Modelica.Units.SI.Resistance | R_T | Transformer resistance | |
| Modelica.Units.SI.Resistance | X_T | Transformer reactance | |
| Modelica.Units.SI.Voltage | V_d0 | Ideal no-load voltage |