modelTransformerYD

Test example with polyphase components

Extends from Modelica.Icons.Example (Icon for runnable examples).

Information

Test example with polyphase components:
Star-connected voltage source feeds via a Y-D-transformer with internal impedance (RT, LT) a load resistor RT.
Using f=5 Hz LT=3mH defines nominal voltage drop of approximately 10 %.
Simulate for 1 second (2 periods) and compare voltages and currents of source, transformer and load.

Parameters

TypeNameDefaultDescription
Integerm3Number of phases
SI.VoltageV1Amplitude of Star-Voltage
SI.Frequencyf5Frequency
SI.InductanceLm1Transformer main inductance
SI.InductanceLT0.003Transformer stray inductance
SI.ResistanceRT0.05Transformer resistance
SI.ResistanceRL1Load Resistance
RealnT1/sqrt((1 - Modelica.Math.cos(2*Modelica.Constants.pi/m))^2 + (Modelica.Math.sin(2*Modelica.Constants.pi/m))^2)Transformer ratio

Components

TypeNameDefaultDescription
Sources.SineVoltagesineVoltage
Basic.StarstarS
Modelica.Electrical.Analog.Basic.GroundgroundS
Ideal.IdealTransformeridealTransformer
Basic.StarstarT
Basic.DeltadeltaT2
Modelica.Electrical.Analog.Basic.GroundgroundT
Basic.ResistortransformerR
Basic.InductortransformerL
Basic.ResistorloadR
Basic.StarstarL
Modelica.Electrical.Analog.Basic.GroundgroundL