modelInfinite_bus_Mashine_old
Information
Infinite bus mashine model.
Модель генератора шин бесконечной мощности.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Real | TgenOff | 1000 | Time of generator's disconnection |
| Real | dTgenOff | 10 | Duration of generator's disconnection |
| Real | Sbaz | sysData.Sbaz | Bazis power, MWA |
| Real | fbaz | sysData.fbaz | Bazic frequency, Hz |
| Real | Pg | Active power | |
| Real | Qg | Reactive power | |
| Real | Ut | 330 | ARV voltage reference value |
| Real | Pnom | 10000 | Set PV-generator power |
| Real | Ugnom | 330 | Nominal voltage |
| Real | cosfi_nom | 0.9 | Nominal maschine power coefficient, p.u. |
| Real | Qmax | 9999 | Текущий предел перевозбуждения, МВар |
| Real | Qmin | -9999 | Текущий предел недовозбуждения, МВар |
| Real | Xq_p | 1.869 | Q-axis synchronous reactance |
| Real | Xs_p | 0.194 | Leakage reactance of stator winding |
| Real | X1d_p | 0.3016 | D-axis transient reactance |
| Real | X2d_p | 0.2337 | D-axis subtransient reactance |
| Real | X2q_p | 0.2337 | Q-axis subtransient reactance |
| Real | Tj_p | 7 | Inertia coefficient |
| Real | Td0 | 10 | D-axis transient time constant, s |
| Real | T2d_p | 0.02 | D-axis subtransient time constant, s |
| Real | T2q_p | 0.05 | Q-axis subtransient time constant, s |
| Real | Mtmax | 1.1 | Turbine overloading coefficient |
| Real | Mtmin | 0 | Turbine minimum-loading coefficient |
| Real | Kemax | 2.0 | Multiplicity of forcing on |
| Real | Kemin | -0.6 | Multiplicity of forcing off |
| Real | PI | 4*atan(1) | PI-constant |
| Real | Wc | 2*PI*fbaz | frequency of electric current fluctuations |
| Real | Xt | 0 | resistance of step-up transformer |
| Real | Ra | 0 | active resistance of generator stator winding |
| Real | Rt | 0 | active resistance of transformer |
| Real | EQ | Auxiliaire EMF of salient-pole generator | |
| Real | Dg | Generator power angle | |
| Real | Uq | D-axis ARV voltage reference value | |
| Real | Ud | Q-axis ARV voltage reference value | |
| Real | Id | D-axis stator current value | |
| Real | Iq | Q-axis stator current value | |
| Real | Eiq | ||
| Real | Ir | field winding current | |
| Real | Uf | field winding voltage | |
| Real | Eq | EMF of generator | |
| Real | Er0 | EMF of generator initial value | |
| Real | PsiR | field winding flow coupling initial value | |
| Real | PsiRD | D-axis damper winding flow coupling initial value | |
| Real | PsiRQ | Q-axis damper winding flow coupling initial value | |
| Real | Er_max | upper bound of EMF of generator | |
| Real | Er_min | lower bound of EMF of generator | |
| Real | Ut_pu | stator voltage, p.u. | |
| Real | Pg_pu | Active power, p.u. | |
| Real | Qg_pu | Reactive power, p.u. | |
| Reactances | |||
| Real | Xd_p | 1.869 | D-axis synchronous reactance |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| OMLET.Interfaces.Pin_v2 | Stator_pin | ||
| OMLET.Interfaces.Signal_pin | Ef_pin | ||
| OMLET.Interfaces.Signal_pin | dUtr_pin | ||
| OMLET.Interfaces.Signal_pin | dWu_pin | ||
| OMLET.Interfaces.Signal_pin | dWf_pin | ||
| OMLET.Interfaces.Signal_pin | dIf_pin | ||
| OMLET.Interfaces.Signal_pin | Ut_pin | ||
| Interfaces.Signal_pin | Mt_pin | ||
| Interfaces.Signal_pin | slip_pin |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| SysData | sysData | ||
| Real | Rf_p | Active resistance of field winding | |
| Real | R1d_p | Active resistance of d-axis damper winding | |
| Real | R1q_p | Active resistance of q-axis damper winding | |
| Real | dUtr | voltage deviation | |
| Real | dWu | frequency deviation | |
| Real | dIf | current deviation | |
| Real | dEr | Electromotive force (EMF) deviation | |
| Real | dWf | frequency deviation | |
| Real | Uf_full | field winding voltage actual value | |
| Real | Xad | D-axis resistance to mutual induction | |
| Real | Xaq | Q-axis resistance to mutual induction | |
| Real | X2dt | D-axis subtransient reactance of generator and transformer | |
| Real | X2qt | Q-axis subtransient reactance of generator and transformer | |
| Real | Rs | Sum resistance of stator winding and step-up transformer | |
| Real | Xsf | Leakage reactance of field winding | |
| Real | Xs1d | D-axis leakage reactance of damping winding | |
| Real | Xs1q | Q-axis leakage reactance of damping winding | |
| Real | X1 | interim reactance №1 | |
| Real | X2 | interim reactance №2 | |
| Real | X3 | interim reactance №3 | |
| Real | Ugen | generator full voltage actual value | |
| Real | Mt_pp | Turbine rotation moment actual value | |
| Real | Pgen | Generator active power actual value | |
| Real | Qgen | Generator reactive power actual value | |
| Real | UdG | ||
| Real | UqG | ||
| Real | IdG | ||
| Real | IqG | ||
| Real | DeltaIJ | ||
| Real | Ssys | system slip | |
| Real | Yr | field winding flow coupling actual value | |
| Real | Yrd | D-axis damper winding flow coupling actual value | |
| Real | Yrq | Q-axis damper winding flow coupling actual value | |
| Real | s | generator slip | |
| Real | DGi | Generator power angle initial value | |
| Real | Me | electrical moment | |
| Real | Yad | D-axis flow coupling of mutual inductance | |
| Real | Yaq | Q-axis flow coupling of mutual inductance | |
| Real | iq | Q-axis generator stator winding current actual value | |
| Real | id | D-axis generator stator winding current actual value | |
| Real | ir | D-axis generator field winding current actual value | |
| Real | ird | D-axis generator damper winding current actual value | |
| Real | irq | Q-axis generator damper winding current actual value | |
| Real | ud | D-axis generator voltage actual value | |
| Real | uq | Q-axis generator voltage actual value | |
| Real | E11d | ||
| Real | E11q | ||
| Real | Xd | D-axis synchronous reactance actual value | |
| Real | Xq | Q-axis synchronous reactance actual value | |
| Real | Xs | Leakage reactance actual value | |
| Real | X1d | D-axis transient reactance actual value | |
| Real | X2d | D-axis subtransient reactance actual value | |
| Real | X2q | Q-axis subtransient reactance actual value | |
| Real | Rf | Active resistance of field winding actual value | |
| Real | R1d | Active resistance of d-axis damper winding actual value | |
| Real | R1q | Active resistance of q-axis damper winding actual value | |
| Real | Tj | Inertia coefficient actual value | |
| Real | f | frequency |