modelSM_initial

Information

Synchronous generator model.

Модель синхронного генератора

Parameters

TypeNameDefaultDescription
OMLET.Data.PQ_CapabilityTablepq_tableOMLET.Data.TVV_500_2
RealTgenOff1000Time of generator's disconnection, s
RealdTgenOff10Duration of generator's disconnection, s
RealSbazsysData.SbazBazic power, MWA
RealfbazsysData.fbazBazic frequency, Hz
RealPg500Active power, MW
RealQgReactive power, MVAR
RealUt20ARV voltage reference value, kV
RealPnom500Nominal maschine active power, MW
RealUgnom20Nominal stator voltage, kV
Realcosfi_nom0.85Nominal maschine power coefficient, p.u.
RealXd_p1.869D-axis synchronous reactance, p.u.
RealXq_p1.869Q-axis synchronous reactance, p.u.
RealXs_p0.194Leakage reactance of stator winding, p.u.
RealX1d_p0.3016D-axis transient reactance, p.u.
RealX2d_p0.2337D-axis subtransient reactance, p.u.
RealX2q_p0.2337Q-axis subtransient reactance, p.u.
RealTj_p7Inertia coefficient, s
RealTd010D-axis transient time constant, s
RealT2d_p0.02D-axis subtransient time constant, s
RealT2q_p0.05Q-axis subtransient time constant, s
RealSigma0.0475Turbine statism coefficient, p.u.
RealTauC_up0.8Time constant of servo motor while valving control, s
RealTregOff50Turbine speed regulator off-time, s
RealTregOn1000Turbine speed regulator on-time, s
RealMtmax1.1Turbine overloading coefficient, p.u.
RealMtmin0Turbine minimum-loading coefficient, p.u.
RealAimp1Fast turbine valving control amplitude, p.u.
RealTimp1000Fast turbine valving control on-time, s
RealdTimp0.2Fast turbine valving control duration, s
RealTauC_down5Time constant of servo motor after valving control end, s
RealTkzOn1000HPP generators dropping on-time, s
RealPg_new0.85New power of HPP, p.u.
RealKemax2.0Multiplicity of forcing on, p.u.
RealKemin-0.6Multiplicity of forcing off, p.u.
RealPI4*atan(1)PI-constant
RealWc2*PI*fbazfrequency of electric current fluctuations
RealXt0.0resistance of step-up transformer and line to IB
RealRa0active resistance of generator stator winding
RealRt0active resistance of transformer
RealEQAuxiliaire EMF of salient-pole generator
RealDgGenerator power angle
RealUqD-axis ARV voltage reference value
RealUdQ-axis ARV voltage reference value
RealIdD-axis stator current value
RealIqQ-axis stator current value
RealEiqsynchronous stator EMF
RealIrfield winding current
RealUffield winding voltage
RealEqEMF of generator
RealEr0EMF of generator initial value
RealPsiRfield winding flow coupling initial value
RealPsiRDD-axis damper winding flow coupling initial value
RealPsiRQQ-axis damper winding flow coupling initial value
RealEr_maxupper bound of EMF of generator
RealEr_minlower bound of EMF of generator
RealMu0Turbine rotation moment initial value
RealUt_pustator voltage, p.u.
RealPg_puActive power, p.u.
RealQg_puReactive power, p.u.

Connectors

TypeNameDefaultDescription
OMLET.Interfaces.Pin_v2Stator_pin
OMLET.Interfaces.Signal_pinEf_pin
OMLET.Interfaces.Signal_pindUtr_pin
OMLET.Interfaces.Signal_pindWu_pin
OMLET.Interfaces.Signal_pindWf_pin
OMLET.Interfaces.Signal_pindIf_pin
OMLET.Interfaces.Signal_pinUt_pin

Components

TypeNameDefaultDescription
SysDatasysData
RealQmaxТекущий предел перевозбуждения, МВар
RealQminТекущий предел недовозбуждения, МВар
RealP_clipped_maxСрезанная P для интерполяции Qmax
RealP_clipped_minСрезанная P для интерполяции Qmin
Integeri_max_dummy
Integeri_min_dummy
RealRf_pActive resistance of field winding, p.u.
RealR1d_pActive resistance of d-axis damper winding, p.u.
RealR1q_pActive resistance of q-axis damper winding, p.u.
RealdUtrvoltage deviation
RealdWufrequency deviation
RealdIfcurrent deviation
RealdErElectromotive force (EMF) deviation
RealdWffrequency deviation
RealUf_fullfield winding voltage actual value
RealXadD-axis resistance to mutual induction
RealXaqQ-axis resistance to mutual induction
RealX2dtD-axis subtransient reactance of generator and transformer
RealX2qtQ-axis subtransient reactance of generator and transformer
RealRsSum resistance of stator winding and step-up transformer
RealXsfLeakage reactance of field winding
RealXs1dD-axis leakage reactance of damping winding
RealXs1qQ-axis leakage reactance of damping winding
RealX1interim reactance в„–1
RealX2interim reactance в„–2
RealX3interim reactance в„–3
RealUgengenerator full voltage actual value
RealRo
RealMuTurbine valve position / moment
RealMt_ppTurbine rotation moment actual value
RealPgenGenerator active power actual value
RealQgenGenerator reactive power actual value
RealUdG
RealUqG
RealIdG
RealIqG
RealDeltaIJ
RealSsyssystem slip
RealYrfield winding flow coupling actual value
RealYrdD-axis damper winding flow coupling actual value
RealYrqQ-axis damper winding flow coupling actual value
Realsgenerator slip
RealDGiGenerator power angle initial value
RealMeelectrical moment
RealYadD-axis flow coupling of mutual inductance
RealYaqQ-axis flow coupling of mutual inductance
RealiqQ-axis generator stator winding current actual value
RealidD-axis generator stator winding current actual value
RealirD-axis generator field winding current actual value
RealirdD-axis generator damper winding current actual value
RealirqQ-axis generator damper winding current actual value
RealudD-axis generator voltage actual value
RealuqQ-axis generator voltage actual value
RealE11dEMF, connected with d-axis damper winding
RealE11qEMF, connected with q-axis damper winding
RealTauCTime constant of servo motor actual value
RealMT_MAXTurbine overloading coefficient actual value
RealMT_MINTurbine minimum-loading coefficient actual value
RealXdD-axis synchronous reactance actual value
RealXqQ-axis synchronous reactance actual value
RealXsLeakage reactance actual value
RealX1dD-axis transient reactance actual value
RealX2dD-axis subtransient reactance actual value
RealX2qQ-axis subtransient reactance actual value
RealRfActive resistance of field winding actual value
RealR1dActive resistance of d-axis damper winding actual value
RealR1qActive resistance of q-axis damper winding actual value
RealTjInertia coefficient actual value
Realffrequency