modelTransformer

Information

The model of a two-winding transformer.

Модель двухобмоточного трансформатора.

Parameters

TypeNameDefaultDescription
General
BooleaninServicetrueTransformer topological condition
RealSbazsysData.SbazBazic power, MVA
RealUnom330Nominal transformer voltage, kV
RealTtOff1000Time of transformer disconnection, s
RealdTtOff10Duration of transformer disconnection, s
RealKoff100000Degree of transformer disconnection, s
BooleandisplayPowerFlowtrueDisplay power flow
G-model parameters
RealR_off1000000
RealG_off1e-5transverse grounding conductivity, p.u.
RealRtrans0.001Active resistance of T-model, Ω
RealXtrans0.01Reactance of T-model, Ω
RealBtrans40Reactive conductivity of T-model, mkS
OLTC
Realk_step0.015OLTC step
Integern_step0current OLTC position

Connectors

TypeNameDefaultDescription
OMLET.Interfaces.Pin_v2inp
OMLET.Interfaces.Pin_v2out

Components

TypeNameDefaultDescription
SysDatasysData
Realkttransformation coeffitient, p.u.
RealU1dD-axis voltage at the beginning of transformer
RealU1qQ-axis voltage at the beginning of transformer
RealU2dD-axis voltage at the end of transformer
RealU2qQ-axis voltage at the end of transformer
RealU1mFull voltage at the beginning of transformer
RealU2mFull voltage at the end of transformer
RealI1dD-axis current at the beginning of transformer
RealI1qQ-axis current at the beginning of transformer
RealI2dD-axis current at the end of transformer
RealI2qQ-axis current at the end of transformer
RealIdlD-axis inductive current of T-model
RealIqlQ-axis inductive current of T-model
RealI1mFull current at the beginning of transformer
RealI2mFull current at the end of transformer
RealP1active power at the beginning of transformer
RealQ1reactive power at the beginning of transformer
RealP2active power at the end of transformer
RealQ2reactive power at the end of transformer
RealRtactual active resistance of transformer
RealXtactual reactive resistance of transformer
RealBtactual reactive conductivity of transformer
RealG_gndcalculation grounding conductivity
RealDU1angle at the beginning of transformer
RealDU2angle at the end of transformer