classImplementation_Notes
Information
English:
I To start working with OMLET, firstly you need to determine 3 basic values: basic power
, basic voltage
, and basic frequency
for example: 1000 MVA, 330 kV and 50 Hz.
The equations within the blocks are written in base relative units, however, the main input and output parameters of the equipment are specified in named units. Below are examples of converting several parameters into base relative units.
- reactivity of synchronous generator (xd, xq, x'd, etc);
- reactivity of transformer;
- reactivity of power transmission line;
- reactivity of external power system;
- reactivity of shunt reactor;
- reactive conductivity of load.
All the active resistances in basic per-units can be calculated in th same way, except resistances of field and damper windings, which can be calculeted dy the formulas below.

II Every scheme needs infinite bus - "big" equivalent generator. It's parameters can be easily calculated using the same method as for a conventional generator. The defining initial parameter for this calculation is the total short-circuit power
, which defines the total power of external system and is determined by the following formula:
,
where Isc - nominal short-circuit cut-off current; Uline - nominal phase-to-phase voltage of the line. If there are several lines of communication with the external power system, the short-circuit power is determined by summing the calculated Ssc value for each line.
Then the infinite bus is equivalent to the number of generators required to provide the total short-circuit power. It is normal, for example, if infinite bus is equivalent to 50 generators of 500 MVA nominal power.
To get quasi-steady-state condition, you need to manually set a dummy load at the infinite power bus connection point so that the power system maintains a balance between generation and consumption. This balance can be easily monitored by the slip value s of the equivalent generator of the external power system - ideally, it must be near zero.
III To investigate transient processes, certain emergency events are needed. Simple switching off (on) is specified by three parameters - time of the element's shutdown (TLineOff, TtOff etc), duration of shutdown (dTLineOff, dTtOff etc) and the degree of its shutdown (Koff) . The latter means either the shutdown of a part of the generation/load, or the shutdown of one circuit or one transformer of the equivalent power line and equivalent transformer, respectively. In real power energy systems the main reason of emergency shutdown is short circuit, which is simulated by ShortCircuitShunt switching on. There are 4 main parameters of ShortCircuitShunt: reactive, active conductivity of short sircuit, time of its start and duration. The fifth parameter, total conductvity of short circuit, is useful, when you need to save the same degree of voltage drop duiring short circuit, varying the ratio between its active and reactive components. To simulate repeated short circuit, you need another ShortCircuitShunt model. The second power transmission line shutdown after its automatic reclosing can be simulated with the help of TLineOff_1, dTLineOff_1 and Koff_1 parameters.
IV LEPSE allows to investigate different means of increasing dynamic stability. The first of them is the changement of Automatic Voltage Regulator (AVR) control coefficients in Excitation_Regulator model as well as setpoints of field forcing, which is realised by logical_switch implementation in AVR model. The second one is series or parallel electrical breaking, Electrical_Braking and Electrical_Braking_Parallel accordingly, which efficiency depends on their active resistanse value. The third mean is fast turbine valving control or turbine fast valving (defined by T_regOff, T_regOn, Aimp, Timp, dTimp values) as well as automatic speed controller (ASC) parameters changement (Sigma and TauCup). The fourth mean is automatic reclosing, which was mentioned before. Finally, the fifth way to increase dynamic stability is generation or load reduction or disabling.
Russian:
I Чтобы начать работать с библиотекой LEPSE, необходимо сначала определить 3 базисные величины: базисная мощность, базисное напряжение и базисную частоту, например: 1000 MВА, 330 кВ и 50 Гц.
Уравнения внутри блоков записаны в базисных относительных единицах, однако основные входные и выходные параметры оборудования задаются в именрванных единицах. Ниже приведены примеры преобразования нескольких параметров в базисные относительные единицы
II