modelDeltaLoad_3Ph

Three-phase delta load

Extends from ThreePhaseComponent (Partial model for inheritance of single-phase base power based on three-phase system base power.).

Information

This is a three-phase delta load model.

The user needs to input the active (P_ab, P_bc and P_ca) and reactive (Q_ab, Q_bc and Q_ca) powers consumed between phases. Since the values come from independent parameters, the model allows the representation of unbalanced loads.

In addition, the model allows the load to be represented as constant power, or as a ZIP model. In the first approach, the powers consumed between phases are kept constant throughout simulation. The latter approach allows the load to be represented as a sum of three terms: constant impedance, constant current and constant power. This means that, depending on voltage levels supplied, the load will consume different values of power.

Parameters

TypeNameDefaultDescription
Power flow data
Types.ApparentPowerS_b (from ThreePhaseComponent)SysData.S_bSystem base
Types.ApparentPowerS_p (from ThreePhaseComponent)SysData.S_b/3Phase base
Types.PerUnitVA1Voltage magnitude for phase A
Types.AngleAngA0Voltage angle for phase A
Types.PerUnitVB1Voltage magnitude for phase B
Types.AngleAngB-2*pi/3Voltage angle for phase B
Types.PerUnitVC1Voltage magnitude for phase C
Types.AngleAngC2*pi/3Voltage angle for phase C
Types.ActivePowerP_ab1e6Initial active power
Types.ReactivePowerQ_ab0Initial reactive power
Types.ActivePowerP_bc1e6Initial active power
Types.ReactivePowerQ_bc0Initial reactive power
Types.ActivePowerP_ca1e6Initial active power
Types.ReactivePowerQ_ca0Initial reactive power
Power flow
IntegerModelType00- Constant Power Model, 1- ZIP Model;
Load Parameters for ZIP Model
RealA_ab0Percentage of Constant Power Load for Line AB [%]
RealB_ab0Percentage of Constant Current Load for Line AB [%]
RealC_ab0Percentage of Constant Impedance Load for Line AB [%]
RealA_bc0Percentage of Constant Power Load for Line BC [%]
RealB_bc0Percentage of Constant Current Load for Line BC [%]
RealC_bc0Percentage of Constant Impedance Load] for Line BC [%]
RealA_ca0Percentage of Constant Power Load for Line CA [%]
RealB_ca0Percentage of Constant Current Load for Line CA [%]
RealC_ca0Percentage of Constant Impedance Load for Line CA [%]

Connectors

TypeNameDefaultDescription
OpenIPSL.Interfaces.PwPinA
OpenIPSL.Interfaces.PwPinB
OpenIPSL.Interfaces.PwPinC

Components

TypeNameDefaultDescription
OpenIPSL.Electrical.SystemBaseSysData (from ThreePhaseComponent)Must add this line in all models

Contents

NameDescription
Voltagesprotected
Coefficientsprotected