functionNu_DittusBoelter

Dittus-Boelter correlation for one-phase flow in a tube Nu = A*Re^alpha*Pr^beta

Information

Dittus-Boelter's correlation for the computation of the heat transfer coefficient in one-phase flows.

Inputs

TypeNameDefaultDescription
SI.ReynoldsNumberReReynolds number
SI.PrandtlNumberPrPrandtl number
RealA0.023Multiplication value
Realalpha0.8Exponent to Reynolds number
Realbeta0.4Exponent to Prandtl number

Outputs

TypeNameDefaultDescription
SI.NusseltNumberNuNusselt number