modelTestElectrical3

Extends from Modelica.Icons.Example (Icon for runnable examples).

Information

The model is designed to test the generator and load components of the Electrical library.

Simulation sequence:

  • t=0 s: The system starts at equilibrium, with the breaker closed. All the active power produced by the generator is consumed by the load, so there is zero power drawn from the grid.
  • t=1 s: The torque (hence the power) is reduced by 20%; the corresponding amount of power is now drawn from the grid.
  • t=3 s: The load is reduced by 10%, so the power drawn from the grid is now reduced to 10% of the nominal value.
  • t=5 s: The breaker is opened. Since there is a deficit of 10% nominal power in the formed island, the frequency starts decreasing with a rate of 10% for each acceleration time Ta=10 s, i.e., by 1%/s, or 0.5 Hz/s.

Simulation Interval = [0...10] sec

Integration Algorithm = DASSL

Algorithm Tolerance = 1e-6

Parameters

TypeNameDefaultDescription
SI.PowerPnom10e6Nominal generator power
SI.Frequencyf0system.fnomNominal network frequency
IntegerNp2Number of polar expansions
SI.AngularVelocityomegan_m2*pi*f0/NpNominal mechanical angular velocity
RealpiModelica.Constants.pi

Components

TypeNameDefaultDescription
Electrical.Generatorgenerator
Electrical.Loadload
Modelica.Mechanics.Rotational.Sources.TorqueprimeMover
Modelica.Blocks.Sources.StepGenTorque
Electrical.Gridgrid
Electrical.BreakerBreaker1
Modelica.Blocks.Sources.StepLocalLoad
Modelica.Blocks.Sources.BooleanStepBreakerCommand
Systemsystem