modelDynamicMultiFluidHeatExchanger

Dynamic one-phase heat exchanger

Extends from ThermoSysPro.Fluid.Interfaces.IconColors (Colors of the static, singular and dynamic model icons).

Information

## Copyright © EDF 2002 - 2026   
## ThermoSysPro Version 4.2

Parameters

TypeNameDefaultDescription
Units.SI.LengthL1Exchanger length
Units.SI.Positionz10Exchanger inlet altitude
Units.SI.Positionz20Exchanger outlet altitude
Realrugosrel_int0.0007Internal relative roughness
Realrugosrel_ext0.0007External relative roughness
Units.SI.DiameterDint0.1Internal diameter
Units.SI.DiameterDext0.11External diameter
IntegerNtubes1Number of pipes in parallel
Units.SI.Thicknesse2.e-3Wall thickness
Units.SI.ThermalConductivitylambda26Wall thermal conductivity
Units.SI.SpecificHeatCapacitycpw1000Wall specific heat capacity (active if dynamic_energy_balance=true)
Units.SI.Densityrhow7800Wall density (active if dynamic_energy_balance=true)
IntegerNs1Number of segments
Units.SI.AbsolutePressureP01.e5Fluid initial pressure (active if steady_state = false and option_temperature=true)
Units.SI.Temperature[Ns]T0fill(290, Ns)Initial fluid temperature (active if steady_state = false and option_temperature=true)
Units.SI.SpecificEnthalpy[Ns]h0fill(1e5, Ns)Initial fluid specific enthalpy (active if steady_state = false and option_temperature=false)
Booleaninertiatruetrue: momentum balance equation with inertia - false: without inertia
Booleanadvectionfalsetrue: momentum balance equation with advection terme - false: without advection terme
Booleandynamic_energy_balancetruetrue: dynamic energy balance equation - false: static energy balance equation
Booleandynamic_mass_balancetruetrue: dynamic mass balance equation - false: static mass balance equation (active if dynamic_energy_balance=true)
Booleansimplified_dynamic_energy_balancetruetrue: simplified dynamic energy balance equation - false: full dynamic energy balance equation (active if dynamic_energy_balance=true and dynamic_mass_balance=true)
Booleansteady_statetruetrue: start from steady state - false: start from T0 (if option_temperature = true) or h0 (if option_temperature=false)(active if dynamic_energy_balance=true)
Booleanoption_temperaturetruetrue: initial temperature is fixed - false: initial specific enthalpy is fixed (active if steady_state=false)
Booleancontinuous_flow_reversalfalsetrue: continuous flow reversal - false: discontinuous flow reversal
Booleandiffusionfalsetrue: energy balance equation with diffusion - false: energy balance equation without diffusion
Fluid › Fluid properties
IF97RegionregionIF97Region.All_regionsIF97 region (active for IF97 water/steam only)

Connectors

TypeNameDefaultDescription
Interfaces.Connectors.FluidInletCfg1
Interfaces.Connectors.FluidOutletCfg2
Interfaces.Connectors.FluidInletCws1
Interfaces.Connectors.FluidOutletCws2

Components

TypeNameDefaultDescription
DynamicOnePhaseFlowPipeDynamicOnePhaseFlowPipe_2
ThermoSysPro.Thermal.HeatTransfer.HeatExchangerWallExchangerWall
Fluid.HeatExchangers.DynamicOnePhaseFlowPipeDynamicOnePhaseFlowPipe_1

Revisions

Author  

Baligh El Hefni