modelValveReferenceValues
Test for Reference Values in Basic and Specific Valve
Extends from Modelica.Icons.Example (Icon for runnable examples).
Information
This test model verifies the safeguards for the reference values
dp_ref and rho_ref in
BasicControlValve and SpecificValveType.
When a valve is parameterized using Kvs,
Cvs_US, or Cvs_UK, the reference values must
remain at their defaults:
dp_ref = 1 barrho_ref = 1000 kg/m3
The model contains correctly parameterized reference valves as well as
valves with modified reference values. The latter use
assertionLevel = AssertionLevel.warning, allowing the
simulation to continue while demonstrating the corresponding assertion
messages.
The test verifies that modifying dp_ref or
rho_ref for standardized flow coefficients is detected,
while valves using the default reference values do not trigger these
assertions.
Components
Contents
| Name | Description |
|---|---|