modelXtH_L1_idContrMFlow_temp_base
Extends from TransiEnt.Basics.Icons.Model (Icon for models).
Information
1. Purpose of model
This model is a base class for heat producers with a pump with ideal mass flow control to get a given outlet temperature. It can be chosen if the outlet set temperature is constant or given by an input.
2. Level of detail, physical effects considered, and physical insight
The mass flow is calculated based on a heat flow rate and a given constant outlet temperature. There is no volume considered.
There are no pressure losses included (pressures at inlet and outlet are given from the outside).
Overheating, i.e. exceeding the set outlet temperature, can be turned on or off.
The model calculates any mass flow that is necessary to reach the given temperature but limits the mass flow so that no flow reversal occurs and that the given maximum mass flow is not exceeded.
If the specific enthalpy at the inlet exceeds the set specific enthalpy, two cases will be distinguished:
- If the set value for the heat flow rate is below the given small value or overheating is not allowed, the mass flow is set to zero and the specific enthalpy is just passed through the fluid ports.
- Otherwise the maximum mass flow rate is set.
The heat flow rate is always calculated according to the actual specific enthalpies and the mass flow rate.
For more details see the equations.
3. Limits of validity
This model is only valid for ideal controls, i.e. ideally tuned controls with no control errors.
4. Interfaces
T_out_set: set point for outlet temperature
Q_flow_set: set point heat flow rate (negative for producers)
fluidPortIn: inlet for fluid
fluidPortOut: outlet for fluid
5. Nomenclature
(no elements)
6. Governing Equations
if inStream(fluidPortIn.h_outflow)>fluidOut.h then
if -Q_flow_set<Q_flow_small or not allowOverheat then
fluidPortOut.m_flow=0;
fluidPortOut.h_outflow=inStream(fluidPortIn.h_outflow);
else
fluidPortOut.h_outflow=Q_flow_set/fluidPortOut.m_flow+inStream(fluidPortIn.h_outflow);
fluidPortOut.m_flow=-m_flow_max; //maximum mass flow to keep the temperature increase at a minimum
end if;
else
fluidPortOut.h_outflow=fluidOut.h;
fluidPortOut.m_flow=-max(0,min(m_flow_max,-Q_flow_set/(fluidPortOut.h_outflow-inStream(fluidPortIn.h_outflow))));
end if;
Q_flow=fluidPortOut.m_flow*(fluidPortOut.h_outflow-inStream(fluidPortIn.h_outflow));
7. Remarks for Usage
The model is only working properly in design flow direction. Reverse flow is not supported!
8. Validation
(no validation necessary)
9. References
(none)
10. Version History
Model created by Carsten Bode (c.bode@tuhh.de), Nov 2018
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Fundamental Definitions | |||
| TILMedia.VLEFluidTypes.BaseVLEFluid | medium | simCenter.fluid1 | Medium to be used |
| Boolean | use_varTemp | false | true if variable temperature input should be used |
| Technical Specifications | |||
| SI.HeatFlowRate | Q_flow_n | 3.5e3 | Nominal heat flow rate |
| SI.Temperature | T_out_set_const | 46 + 273.15 | Constant outlet temperature |
| SI.MassFlowRate | m_flow_max | 1e10 | Maximum mass flow |
| Boolean | allowOverheat | false | true if the heat producer is allowed to supply heat even if the outlet temperature is higher than T_out_const then |
| Numerical Stability | |||
| SI.HeatFlowRate | Q_flow_small | 1 | Small heat flow rate under which the heat supply stops |
| Statistics | |||
| TransiEnt.Basics.Types.TypeOfResource | typeOfResource | TransiEnt.Basics.Types.TypeOfResource.Conventional | Select the kind of resource |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| TransiEnt.Basics.Interfaces.Thermal.FluidPortIn | fluidPortIn | ||
| TransiEnt.Basics.Interfaces.Thermal.FluidPortOut | fluidPortOut | ||
| TransiEnt.Basics.Interfaces.General.TemperatureIn | T_out_set | T_out_set_in | Setpoint value of the output temperature |
| TransiEnt.Basics.Interfaces.Thermal.HeatFlowRateIn | Q_flow_set | Setpoint value of the heat flow, should be negative |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| TransiEnt.SimCenter | simCenter | ||
| TransiEnt.ModelStatistics | modelStatistics | ||
| TILMedia.Internals.VLEFluidConfigurations.FullyMixtureCompatible.VLEFluid_pT | fluidOut | ||
| TransiEnt.Components.Statistics.Collectors.LocalCollectors.HeatingPlantCost | collectCosts_HeatProducer | ||
| TransiEnt.Components.Statistics.Collectors.LocalCollectors.CollectHeatingPower | collectHeatingPower | ||
| SI.Temperature | T_out_set_in | ||
| SI.HeatFlowRate | Q_flow |