modelULTC_VoltageControl

Under Load Tap Changer, continous model, secondary voltage control

Information

Development level

2

Reference

PSAT Manual 2.1.8

Last update

15/07/2015

Author

MAA Murad, SmarTS Lab, KTH Royal Institute of Technology

Contact

luigiv@kth.se

Parameters

TypeNameDefaultDescription
Power flow data
RealSb100System base power (MVA)
RealVbus1400000Sending end Bus nominal voltage (V)
RealVbus2100000Receiving end Bus nominal voltage (V)
RealSn100Power rating (MVA)
RealVn400000Voltage rating (V)
Realfn50Frequency rating (Hz)
RealV_01.008959700699460Voltage magnitude of the controlled bus (pu)
Realm00.98Initial tap ratio
ULTC data
RealkT4Nominal tap ratio (V1/V2)
RealH0.001Integral deviation (pu)
RealK0.10Inverse time constant (1/s)
Realm_max0.98Maximum tap ratio (p.u./p.u.)
Realm_min0.9785Minimum tap ratio (p.u./p.u.)
Realdeltam0Tap ratio step (p.u./p.u.)
Realv_ref1.0Reference voltage (power) (pu)
RealxT0.001Transformer reactance (pu)
RealrT0.1Transformer resistance (pu)
Reald0.05Dead zone percentage

Connectors

TypeNameDefaultDescription
iPSL.Connectors.PwPinp
iPSL.Connectors.PwPinn

Components

TypeNameDefaultDescription
RealmTap ratio
RealvkVoltage at primary, p.u.
RealvmVoltage at secondary p.u.
RealanglevkAngle at primary
RealanglevmAngle at secondary

Revisions

Copyright 2015-2016 RTE (France), SmarTS Lab (Sweden), AIA (Spain) and DTU (Denmark)

The authors can be contacted by email: info@itesla-ipsl.org

This Source Code Form is subject to the terms of the Mozilla Public License, v. 2.0.

If a copy of the MPL was not distributed with this file, You can obtain one at http://mozilla.org/MPL/2.0.