modelExponentialRecovery

Exponential Recovery Load

Extends from BaseClasses.baseLoad.

Information

Development level

3

Reference

Exponential Recovery Load, PSAT Manual 2.1.8

Last update

September 2015

Author

Joan Russinol, SmarTS Lab, KTH Royal Institute of Technology

Contact

luigiv@kth.se

Parameters

TypeNameDefaultDescription
RealSn (from baseLoad)S_bPower rating (MVA)
RealTp1Active power time constant (s)
RealTq1Reactive power time constant (s)
Realalpha_s2Static active power exponent
Realalpha_t1.5Dynamic active power exponent
Realbeta_s2Static reactive power exponent
Realbeta_t1.5Dynamic reactive power exponent
Power flow data
RealV_b (from pfComponent)400Base voltage of the bus (kV)
RealV_0 (from pfComponent)1Voltage magnitude (pu)
Realangle_0 (from pfComponent)0Voltage angle (deg)
RealP_0 (from pfComponent)1Active power (MW)
RealQ_0 (from pfComponent)0Reactive power (MVAr)
RealS_b (from pfComponent)SysData.S_bSystem base power (MVA)
Realfn (from pfComponent)SysData.fnSystem Frequency (Hz)

Connectors

TypeNameDefaultDescription
iPSL.Connectors.PwPinp (from baseLoad)

Components

TypeNameDefaultDescription
SystemBaseSysData (from pfComponent)Must add this line in all models
RealV (from baseLoad)Voltage magnitude (pu)
RealAngle_V (from baseLoad)voltage angle (rad)
RealP (from baseLoad)Active power (pu)
RealQ (from baseLoad)Reactive power (pu)
RealpsStatic real power absorption (pu)
RealptTransient real power absorption (pu)
RealqsStatic imaginary power absorption (pu)
RealqtTransient imaginary power absorption (pu)

Revisions

Copyright 2015-2016 RTE (France), SmarTS Lab (Sweden), AIA (Spain) and DTU (Denmark)

The authors can be contacted by email: info@itesla-ipsl.org

This Source Code Form is subject to the terms of the Mozilla Public License, v. 2.0.

If a copy of the MPL was not distributed with this file, You can obtain one at http://mozilla.org/MPL/2.0.