modelbaseLoad

Extends from iPSL.Electrical.Essentials.pfComponent (Partial model containing all the Data for entering Power Flow data).

Information

Development level

3

Parameters

TypeNameDefaultDescription
ComplexS_pP_0 + j*Q_0Consumption of original constant power load (MVA)
ComplexS_iComplex(0)Consumption of original constant current load (MVA)
ComplexS_yComplex(0)Consumption of original constant shunt admittance load (MVA)
Complexa1 + j*0Load transfer fraction for constant current load
Complexb0 + j*1Load transfer fraction for constant shunt admittance load
RealPQBRAK0.7Constant power characteristic threshold
Integercharacteristic1
Power flow data
RealV_b (from pfComponent)400Base voltage of the bus (kV)
RealV_0 (from pfComponent)1Voltage magnitude (pu)
Realangle_0 (from pfComponent)0Voltage angle (deg)
RealP_0 (from pfComponent)1Active power (MW)
RealQ_0 (from pfComponent)0Reactive power (MVAr)
RealS_b (from pfComponent)SysData.S_bSystem base power (MVA)
Realfn (from pfComponent)SysData.fnSystem Frequency (Hz)

Connectors

TypeNameDefaultDescription
iPSL.Connectors.PwPinp

Components

TypeNameDefaultDescription
SystemBaseSysData (from pfComponent)Must add this line in all models
RealangleBus voltage angle (rad)
RealvBus voltage magnitude (pu)
RealPActive power consumption (pu)
RealQReactive power consumption (pu)

Revisions

Copyright 2015-2016 RTE (France), SmarTS Lab (Sweden), AIA (Spain) and DTU (Denmark)

The authors can be contacted by email: info@itesla-ipsl.org

This Source Code Form is subject to the terms of the Mozilla Public License, v. 2.0.

If a copy of the MPL was not distributed with this file, You can obtain one at http://mozilla.org/MPL/2.0.