modelGE_WT
Information
Development level |
2 |
Reference |
GE Wind Turbine Generator http://doi.org/10.1109/PES.2003.1267470 |
Last update |
July 2015 |
Author |
Maxime Baudette, SmarTS Lab, KTH Royal Institute of Technology |
Contact |
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Real | _V0 | 1.03 | Terminal Voltage from Power Flow |
| Real | _Ang0 | 0.421202138172605 | Terminal Angle from Power Flow |
| Real | _P0 | 1.62 | Active Power from Power Flow |
| Real | _Q0 | -0.370492231185345 | Reactive Power from Power Flow |
| Real | GEN_base | 180 | Base Power from the Electrical Generator |
| Real | WT_base | 162 | Base Power from the Turbine |
| Real | SYS_base | 100 | Base Power from the power system |
| Real | freq | 60 | Steady state Frequency of the power system |
| Real | poles | 3 | Number of pole pairs |
| Real | Tp | 0.3 | Time Constant Pitch command |
| Real | Kpp | 150.0 | Pitch Control gain |
| Real | Kip | 25.0 | Gain of integrator of Pitch Control |
| Real | Kpc | 3.0 | Pitch Compensation gain |
| Real | Kic | 30.0 | Gain of integrator of Pitch Compensation |
| Real | pimax | 27.0 | Maximum pitch angle |
| Real | pimin | 0.0 | minimum pitch angle |
| Real | pirat | 10.0 | maximum variation rate of pitch angle |
| Real | pwmax | 1.12 | Maximal power taken from the wind |
| Real | pwmin | 0.1 | Minimal power taken from the wind |
| Real | pwrat | 0.45 | maximum variation rate of power taken from the wind |
| Real | Kptrq | 3.0 | Gain Torque Controller |
| Real | Kitrq | 0.6 | Gain of integrator of Torque Controller |
| Real | Tpc | 0.05 | Time Constant Torque controller |
| Real | KQi | 0.1 | Gain constant of first PI in DFIG electrical control model |
| Real | KVi | 40 | Gain constant of second PI in DFIG electrical control model |
| Real | xiqmax | 0.4 | Up saturation of second PI in DFIG electrical control model |
| Real | xiqmin | -0.5 | Down saturation of second PI in DFIG electrical control model |
| Real | Kpllp | 30 | |
| Real | Xpp | 0.8 | |
| Real | qmax | 0.312 | |
| Real | qmin | -0.436 | |
| Real | nmass | 2 | Mono-mass or Two-mass model |
| Real | Hg | 0.62 | Inertia 2 |
| Real | H | 4.33 | Inertia |
| Real | Ktg | 1.11 | Gain for 2 mass model |
| Real | Dtg | 1.5 | Damping |
| Real | Kl | 56.6 |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| iPSL.Connectors.PwPin | pwPin1 | ||
| Modelica.Blocks.Interfaces.RealInput | Wind_Speed |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Real | P | Active Power produced in SYS_base | |
| Real | Q | Reactive Power produced in SYS_base | |
| Turbine.Turbine_Model | turbine_Model1 | ||
| Electrical_Control.Electrical_Control | electrical_Control1 | ||
| Generator.Generator | generator1 |
Contents
| Name | Description |
|---|---|
| cp_initprotected | |
| get_Vwprotected | |
| get_thetaprotected |
Revisions
Copyright 2015-2016 RTE (France), SmarTS Lab (Sweden), AIA (Spain) and DTU (Denmark)
- RTE: http://www.rte-france.com
- SmarTS Lab, research group at KTH: https://www.kth.se/en
- AIA: http://www.aia.es/en/energy
- DTU: http://www.dtu.dk/english
The authors can be contacted by email: info@itesla-ipsl.org
This Source Code Form is subject to the terms of the Mozilla Public License, v. 2.0.
If a copy of the MPL was not distributed with this file, You can obtain one at http://mozilla.org/MPL/2.0.