Effective air leakage area
This model describes the one-directional pressure driven air
flow through a crack-like opening, using the equation
V̇ = C
Δpm,
where V̇ is the volume flow rate, C is a flow
coefficient and m is the flow exponent. The flow coefficient
is
C = L
CD,Rat ΔpRat(0.5-m)
(2/ρ0)0.5,
where L is the effective air leakage area,
CD,Rat is the discharge coefficient at the
reference condition, ΔpRat is the pressure drop
at the rating condition, and ρ0 is the mass
density at the medium default pressure, temperature and
humidity.
The effective air leakage area L can be obtained, for
example, from the ASHRAE fundamentals (ASHRAE, 1997, p. 25.18). In
the ASHRAE fundamentals, the effective air leakage area is based on
a reference pressure difference of ΔpRat = 4 Pa
and a discharge coefficient of CD,Rat = 1. A
similar model is also used in the CONTAM software (Dols and Walton,
2002). Dols and Walton (2002) recommend to use for the flow
exponent m=0.6 to m=0.7 if the flow exponent is not
reported with the test results.
References
- ASHRAE, 1997. ASHRAE Fundamentals, American
Society of Heating, Refrigeration and Air-Conditioning Engineers,
1997.
- Dols and Walton, 2002. W. Stuart Dols and George N.
Walton, CONTAMW 2.0 User Manual, Multizone Airflow and
Contaminant Transport Analysis Software, Building and Fire
Research Laboratory, National Institute of Standards and
Technology, Tech. Report NISTIR 6921, November, 2002.
- Michael Wetter.
Multizone Airflow Model in Modelica. Proc. of the 5th
International Modelica Conference, p. 431-440. Vienna, Austria,
September 2006.
- February 2, 2022, by Michael Wetter:
Revised implementation.
This is for IBPSA,
#1436.
- Apr 6, 2021, by Klaas De Jonge:
Changes due to changes in the baseclass, velocity is now a
top-level variable.
- June 24, 2018, by Michael Wetter:
Removed parameter lWet as it is only used to compute
the Reynolds number, and the Reynolds number is not used by this
model. Also removed the variable Re for the Reynolds
number.
Changed base class to remove the parameters A and
CD which are not used by this model.
This change is non-backward compatible.
This is for IBPSA,
#932.
- May 30, 2018, by Michael Wetter:
Improved documentation for IBPSA,
#546.
- April 24, 2017, by Filip Jorissen:
Corrected error in computation of A which was
A=CD/CDRat * L * dpRat^(0.5-m) rather than
A=CDRat/CD * L * dpRat^(0.5-m).
See #743.
- January 22, 2016, by Michael Wetter:
Corrected type declaration of pressure difference. This is for
#404.
- October 8, 2013 by Michael Wetter:
Changed the parameter useConstantDensity to
useDefaultProperties to use consistent names within
this package. A conversion script can be used to update this
parameter.
- July 20, 2010 by Michael Wetter:
Migrated model to Modelica 3.1 and integrated it into the Buildings
library.
- February 10, 2005 by Michael Wetter:
Released first version.
Generated at 2026-04-05T18:18:26Z by OpenModelicaOpenModelica 1.26.3 using