.AixLib.Fluid.Actuators.Valves.ExpansionValves.Utilities.FlowCoefficient.SpecifiedFlowCoefficients.Poly_R22_EEV_16

Information

This model contains a calculation procedure for flow coefficients presented by Li (2013).

"Power approaches" border="1" cellspacing="0" cellpadding="2" style="border-collapse:collapse;">
Reference Formula Refrigerants Validity Tcondensing Validity Tevaporating Validity Tsubcooling
Li2013 C = a1 + a2*opening + a3*opening^2 + a4*opening*(Tsubcooling/Tcrit) + a5*(Tsubcooling/Tcrit) + a6*(Tsubcooling/Tcrit)^2 R22 30 - 50 °C 0 - 30 °C 1.5 - 15 °C

References

Li, W. (2013): Simplified modeling analysis ofmass flow characteristics in electronic expansion valve. In: Applied Thermal Engineering 53(1), S. 8–12

Revisions


Generated at 2024-11-27T19:25:31Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos