modelPoly_R134a_170_Reciprocating

Reciporating Compressor - R134a - 170 cm³ - Polynomial

Extends from PolynomialVolumetricEfficiency (Model describing volumetric efficiency based on polynomial approach).

Information

This model contains a calculation procedure for the isentropic efficiency presented by Li (2013).

"Power approaches" border="1" cellspacing="0" cellpadding="2" style="border-collapse:collapse;">
Reference Formula Refrigerants Validity ncompressor Validity Πpressure
Li2013 ηvol = ηvolRef * (a1 + a2*(n/nref) + a3*(n/nref)^2) R22,R134a 30 - 120 4 - 12

References

W. Li (2013): Simplified steady-state modeling for variable speed compressor. In: Applied Thermal Engineering 50(1), S. 318–326

Parameters

TypeNameDefaultDescription
Modelling approach
Types.VolumetricPolynomialModelspolyMod (from PolynomialVolumetricEfficiency)Types.VolumetricPolynomialModels.Karlsson2007Chose predefined polynomial model for flow coefficient
Real[:]a (from PolynomialVolumetricEfficiency)Multiplication factors for each summand
Real[:]b (from PolynomialVolumetricEfficiency)Exponents for each summand
IntegernT (from PolynomialVolumetricEfficiency)size(a, 1)Number of terms used for the calculation procedure
Real[:]c (from PolynomialVolumetricEfficiency){1}Coefficients used for correction factors if needed
Reference properties
Modelica.Units.SI.FrequencyrotSpeRef (from PolynomialVolumetricEfficiency)9.334Reference rotational speed

Components

TypeNameDefaultDescription
Modelica.Units.SI.EfficiencyepsRef (from PartialEfficiency)Ratio of the real and the ideal displacement volume
Modelica.Units.SI.VolumeVDis (from PartialEfficiency)Displacement volume
RealpiPre (from PartialEfficiency)Ratio of compressor's outlet and inlet pressure
Modelica.Units.SI.FrequencyrotSpe (from PartialEfficiency)Compressor's current rotational speed
Medium.ThermodynamicStatestaInl (from PartialEfficiency)Thermodynamic state at compressor's inlet
Medium.ThermodynamicStatestaOut (from PartialEfficiency)Thermodynamic state at compressor's outlet
Modelica.Units.SI.TemperatureTAmb (from PartialEfficiency)Ambient temperature
Modelica.Units.SI.EfficiencylamH (from PartialVolumetricEfficiency)Overall volumetric efficiency
Real[nT]p (from PolynomialVolumetricEfficiency)Array that contains all coefficients used for the calculation procedure
Real[2]corFac (from PolynomialVolumetricEfficiency)Array of correction factors used if efficiency model proposed in literature differs from efficiency model defined in PartialCompressor model

Revisions

  • October 23, 2017, by Mirko Engelpracht:
    First implementation (see issue 467).