Pump on/off controller for a solar thermal system.
This controller outputs whether the pump should be commanded on
or off based on the incident solar radiation, the collector inlet
temperature, and the system parameters. The pump is commanded on
when the incident solar radiation is greater than the critical
radiation plus the offset delQ_flow, and it is
switched off if the incident solar radiation is below the critical
radiation.
The critical radiation is defined per Equation 6.8.2 in Duffie and Beckman (2006). It is
GTC=(FRUL (TIn-TEnv)) /(FR(τα))
where GTC is the critical solar radiation, FRUL is the heat loss coefficient, TIn is the inlet temperature, TEnv is the ambient temperature, and FR(τα) is the maximum efficiency.
J.A. Duffie and W.A. Beckman 2006, Solar Engineering of Thermal
Processes (3rd Edition), John Wiley & Sons, Inc.
AixLib.Obsolete
package.