Block of a controller for set point tracking with a hysteresis element that switches the controller on and off, and a timer that prevents the controller to short cycle.
The controller is similar to
Annex60.Controls.Continuous.PIDHysteresis but in addition,
it has a timer that prevents the controller from switching to on
too fast. When the controller switches off, the timer starts and
avoids the controller from switching on until minOffTime
seconds elapsed.
limitsAtInit
because it is no longer
used in the PID controller.
strict=true
in order to avoid events when the controller saturates.
Also assigned propogated values to be final
.
This is for
issue 433.
eOn
.