An air volume to represent a staircase element for a scalable air flow benchmark.
This is a very simple room representation. The model is intended to roughly approximate a first
order response of the zone to changes in outdoor air temperature. This is achieved by a thermal
resistance in model conRoom
and the capitancy of the mixing volume represented by the
value for mSenFac
. The G-Value of conRoom
is approximated by the area of
one outside wall multiplied with a U-Value of 1 W/(m² K). The value for mSenFac
has been estimated from comparisons with other room models as shown in
Annex60.Experimental.Benchmarks.AirFlow.Examples.ZoneStepResponse. For this model, a value for
mSenFac
slightly lower than in
Annex60.Experimental.Benchmarks.AirFlow.Components.SimpleZone has been chosen.
port_a_toHallway
and port_b_toHallway
should be connected to the
corresponding ports of a hallway model. port_a_top
and port_b_top
can be
connected to another staircase model via its respective port_a_bot
and
port_b_bot
.
Inspired by Annex60.Airflow.Multizone.Validation.ThreeRoomsContam
Name | Description |
---|---|
Medium | Medium in the component |
ThermalConductor
and the
PrescripedTemperature
model. This is for
#266,
to work with Dymola 2016 in pedantic mode.