An air volume to represent a hallway element for a scalable air flow benchmark.
This is a very simple room representation. The model is intended to roughly approximate a first
order response of the zone to changes in outdoor air temperature. This is achieved by a thermal
resistance in model conRoom and the capitancy of the mixing volume represented by the
value for mSenFac. The G-Value of conRoom is approximated by the area of
one outside wall multiplied with a U-Value of 1 W/(m² K). The value for
mSenFac has been estimated from comparisons with other room models as shown in
Annex60.Experimental.Benchmarks.AirFlow.Examples.ZoneStepResponse. For this model, a value for
mSenFac slightly lower than in
Annex60.Experimental.Benchmarks.AirFlow.Components.SimpleZone has been chosen.
port_a_toZone and port_b_toZone should be connected to the corresponding
ports of a zone model, port_a_toOutside and port_b_toOutside should be
connected to the corresponding ports of the OutsideEnvironment. port_a2
and port_b2 can be connected to either a staircase model or to further hallway elements
via their respective port_a1 and port_b2.
This model is following the approach used in Annex60.Airflow.Multizone.Validation.ThreeRoomsContam, only in a more modularized way in order to be part of a scalable benchmark.
Inspired by Annex60.Airflow.Multizone.Validation.ThreeRoomsContam
| Name | Description |
|---|---|
| Medium in the component |
ThermalConductor and the
PrescripedTemperature model. This is for
#266,
to work with Dymola 2016 in pedantic mode.