.Annex60.Fluid.Actuators.BaseClasses.PartialTwoWayValve

Information

Partial model for a two way valve. This is the base model for valves with different opening characteristics, such as linear, equal percentage, quick opening or pressure-independent.

To prevent the derivative d/dP (m_flow) to be infinite near the origin, this model linearizes the pressure drop versus flow relation ship. The region in which it is linearized is parameterized by

  m_turbulent_flow = deltaM * m_flow_nominal

Because the parameterization contains Kv_SI, the values for deltaM and dp_nominal need not be changed if the valve size changes.

In contrast to the model in Modelica.Fluid, this model uses the parameter Kv_SI, which is the flow coefficient in SI units, i.e., it is the ratio between mass flow rate in kg/s and square root of pressure drop in Pa.

Options

This model allows different parameterization of the flow resistance. The different parameterizations are described in Annex60.Fluid.Actuators.BaseClasses.ValveParameters.

Implementation

The two way valve models are implemented using this partial model, as opposed to using different functions for the valve opening characteristics, because each valve opening characteristics has different parameters.

Revisions


Generated at 2024-12-03T19:25:34Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos