.Annex60.Fluid.Movers.BaseClasses.Characteristics.pressure

Information

This function computes the fan static pressure raise as a function of volume flow rate and revolution in the form

Δp = rN2   s(V̇/rN, d),

where Δp is the pressure rise, rN is the normalized fan speed, is the volume flow rate and d are performance data for fan or pump power consumption at rN=1.

Implementation

The function s(·, ·) is a cubic hermite spline. If the data d define a monotone decreasing sequence, then s(·, d) is a monotone decreasing function.

The function allows rN to be zero.

Interface

function pressure
  extends Modelica.Icons.Function;
  input Modelica.SIunits.VolumeFlowRate V_flow "Volumetric flow rate";
  input Real r_N(unit = "1") "Relative revolution, r_N=N/N_nominal";
  input Real d[:] "Derivatives of flow rate vs. pressure at the support points";
  input Modelica.SIunits.PressureDifference dpMax(displayUnit = "Pa") "Maximum pressure drop at nominal speed, for regularisation";
  input Modelica.SIunits.VolumeFlowRate V_flow_max "Maximum flow rate at nominal speed, for regularisation";
  input Annex60.Fluid.Movers.BaseClasses.Characteristics.flowParametersInternal per "Pressure performance data";
  output Modelica.SIunits.PressureDifference dp(displayUnit = "Pa") "Pressure raise";
end pressure;

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos