This example tests the step response of the SimpleZone model for
the airflow benchmark. It uses the weather file
STEP_TMY.mos, that implements a 5 Kelvin step
at t=400 000 seconds. In the Buildings library, the room
model of BESTEST 600 FF needs around 4-5 hours in order to
reach 2/3 of the maximum step response to this weather file.
This time constant is approximated with a value of mSenFac =
75 for the mixing volume of the zone.
The mass flow rate of air to the zone is 0.05 kg/s, which approximates an air exchange rate of 3 times the air volume per hour.