Evaporator or condenser with refrigerant experiencing constant
temperature phase change
Model for a constant temperature evaporator or condenser based
on a ε-NTU heat exchanger model.
The heat exchanger effectiveness is calculated from the number
of transfer units (NTU):
ε = 1 - exp(UA ⁄ (ṁ
cp))
Optionally, this model can have a flow resistance. If no flow
resistance is requested, set dp_nominal=0.
Limitations
This model does not consider any superheating or supercooling on
the refrigerant side. The refrigerant is considered to exchange
heat at a constant temperature throughout the heat exchanger.
- March 7, 2022, by Michael Wetter:
Removed massDynamics.
This is for #1542.
- May 27, 2017, by Filip Jorissen:
Regularised heat transfer around zero flow.
This is for #769.
- April 12, 2017, by Michael Wetter:
Corrected invalid syntax for computing the specific heat
capacity.
This is for #707.
- October 11, 2016, by Massimo Cimmino:
First implementation.