.BuildSysPro.IBPSA.Fluid.HeatExchangers.Radiators.RadiatorEN442_2

Information

This is a model of a radiator that can be used as a dynamic or steady-state model. The required parameters are data that are typically available from manufacturers that follow the European Norm EN 442-2.

However, to allow for varying mass flow rates, the transferred heat is computed using a discretization along the water flow path, and heat is exchanged between each compartment and a uniform room air and radiation temperature. This discretization is different from the computation in EN 442-2, which may yield water outlet temperatures that are below the room temperature at low mass flow rates. Furthermore, rather than using only one room temperature, this model uses a room air and room radiation temperature.

The transferred heat is modeled as follows: Let N denote the number of elements used to discretize the radiator model. For each element i ∈ {1, … , N}, the convective and radiative heat transfer Qic and Qir from the radiator to the room is

Qic = sign(Ti-Ta) (1-fr) UA ⁄ N |Ti-Ta|n

Qir = sign(Ti-Tr) fr UA ⁄ N |Ti-Tr|n

where Ti is the water temperature of the element, Ta is the temperature of the room air, Tr is the radiative temperature, 0 < fr < 1 is the fraction of radiant to total heat transfer, UA is the UA-value of the radiator, and n is an exponent for the heat transfer. The model computes the UA-value by numerically solving the above equations for given nominal heating power, nominal temperatures, fraction radiant to total heat transfer and exponent for heat transfer.

The parameter energyDynamics (in the Assumptions tab), determines whether the model computes the dynamic or the steady-state response. For the transient response, heat storage is computed using a finite volume approach for the water and the metal mass, which are both assumed to be at the same temperature.

The default parameters for the heat capacities are valid for a flat plate radiator without fins, with one plate of water carying fluid, and a height of 0.42 meters.

Revisions


Generated at 2024-11-22T19:25:38Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos