Hypothesis and equations
This is an air/air heat pump with on/off (intermittently controlled) operation (fixed speed) for the heating mode only.
The model is minimalist in terms of parameters to inform and is based on an empirical approach to determining the power in steady state according to indoor and outdoor temperatures conditions. The transitional regime is modelled using a time constant for the power supplied.
The HP operates in all or nothing. Start and stop phases are given by the associated control system. To protect the machine, it is common that minimum on and off times are defined (DtminOn and DtminOff), they intervene in internal control of the machine.
Bibliography
none
Instructions for use
Four parameter choices are possible: WARNING! Be sure to replace the default setting options that are not used because they may be used to simulate the default configuration
Although the need to ensure the replacement of default values to use the default configuration, it is possible for advanced users to modify the HP performance curve using the mode 3 or 4, then go in mode 1 or 2 to modulate the HP power from performances defined above.
Known limits / Use precautions
For empirical approach, pay special attention to the choice of operating temperatures range.
Degradation related to icing/de-icing is rather grossly given without dynamic (10% degradation of the power supplied for outside temperatures below 2°C).
Not suitable for variable speed.
Validations
Validated model with TIL - Hubert Blervaque, Sila Filfli 05/2012
--------------------------------------------------------------
Licensed by EDF under a 3-clause BSD-license
Copyright © EDF 2009 - 2023
BuildSysPro version 3.6.0
Author : Hubert BLERVAQUE, Sila FILFLI, EDF (2012)
--------------------------------------------------------------
Hubert Blervaque - novembre 2013 : MAJ de la description des paramètres