.BuildingSystems.Fluid.Geothermal.Borefields.BaseClasses.Boreholes.BaseClasses.InternalResistancesOneUTube

Information

This model simulates the internal thermal resistance network of a borehole segment in the case of a single U-tube borehole using the method of Bauer et al. (2011) and computing explicitely the fluid-to-ground thermal resistance Rb and the grout-to-grout resistance Ra as defined by Claesson and Hellstrom (2011) using the multipole method.

References

J. Claesson and G. Hellstrom. Multipole method to calculate borehole thermal resistances in a borehole heat exchanger. HVAC&R Research, 17(6): 895-911, 2011.

D. Bauer, W. Heidemann, H. Müller-Steinhagen, and H.-J. G. Diersch. Thermal resistance and capacity models for borehole heat exchangers . International Journal Of Energy Research, 35:312-320, 2011.

Revisions


Generated at 2024-11-26T19:26:15Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos