This validation case applies the asymetrical synthetic load profile developed
by Pinel (2003) over a 20 year period by directly injecting the heat at the
borehole wall in the ground temperature response model. The difference between
the resulting borehole wall temperature and the same temperature precalculated
by using a fast Fourier transform is calculated with the add
component. The fast Fourier transform calculation was done using the same
g-function as was calculated by
BuildingSystems.Fluid.Geothermal.Borefields.BaseClasses.HeatTransfer.ThermalResponseFactors.gFunction.
Pinel, P. 2003. Amélioration, validation et implantation d’un algorithme de calcul pour évaluer le transfert thermique dans les puits verticaux de systèmes de pompes à chaleur géothermiques, M.A.Sc. Thesis, École Polytechnique de Montréal.