.BuildingSystems.Fluid.MassExchangers.ConstantEffectiveness

Information

Model for a heat and moisture exchanger with constant effectiveness.

This model transfers heat and moisture in the amount of

  QSen = epsS * Q_max,
  m    = epsL * mWat_max,

where epsS and epsL are constant effectiveness for the sensible and latent heat transfer, Q_max is the maximum sensible heat that can be transferred and mWat_max is the maximum moisture that can be transferred.

For a sensible heat exchanger, use BuildingSystems.Fluid.HeatExchangers.ConstantEffectiveness instead of this model.

This model can only be used with medium models that define the integer constant Water which needs to be equal to the index of the water mass fraction in the species vector.