This function computes the density as a function of temperature.

Implementation

The function is based on the IDA implementation in therpro.nmf, which implements

d := 1000.12 + 1.43711e-2*T_degC -
 5.83576e-3*T_degC^2 + 1.5009e-5*T_degC^3;
 

This has been converted to Kelvin, which resulted in the above expression. In addition, below 5 °C and above 100 °C, the density is replaced by a linear function to avoid inflection points. This linear extension is such that the density is once continuously differentiable.