.Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.ASHRAE62_1.SumZone

Information

This sequence sums up zone level minimum outdoor airflow setpoints and find the maximum outdoor air fraction. It is implemented according to Section 5.16.3.1 of ASHRAE Guideline G36, May 2020.

It calculates following values:

  1. Sum of the adjusted population component breathing zone flow rate VAdjPopBreZon_flow for all zones that are in all zone groups in occupied mode, VSumAdjPopBreZon_flow.
  2. Sum of the adjusted area component breathing zone flow rate VAdjAreBreZon_flow for all zones that are in all zone groups in occupied mode, VSumAdjAreBreZon_flow.
  3. Sum of the zone primary airflow rates VZonPri_flow for all zones in all zone groups that are in occupied mode,VSumZonPri_flow.
  4. Maximum zone outdoor air fraction for all zones in all zone groups that are in occupied mode, uOutAirFra_max.

See Buildings.Controls.OBC.ASHRAE.G36.VentilationZones.ASHRAE62_1.Setpoints for the detailed description of the inputs VAdjPopBreZon_flow, VAdjAreBreZon_flow and VMinOA_flow.

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos