.Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.ASHRAE62_1

Information

This package contains sequences to set the minimum outdoor airflow setpoint for compliance with the ventilation rate procedure of ASHRAE 62.1. It is implemented according to Section 5.16.3.1 of ASHRAE Guideline G36, May 2020.

Contents

NameDescription
 AHUOutdoor airflow related calculations at the AHU level
 SumZoneCalculate the sum of zone level setpoints
 ValidationCollection of validation models

Revisions