This sequence sums up zone level minimum outdoor airflow setpoints when complying with California Title 24 ventilation requirements. It is implemented according to Section 5.16.3.2 of ASHRAE Guideline G36, May 2020.
It calculates following values:
VZonAbsMin_flow
for all zones in all zone groups that are in occupied mode.
VZonDesMin_flow
for all zones in all zone groups that are in occupied mode.
yMaxCO2
.
See the zone absolute and design minimum outdoor airflow setpoint
VZonAbsMin_flow
and VZonDesMin_flow
from
Buildings.Controls.OBC.ASHRAE.G36.VentilationZones.Title24.Setpoints for the detailed
description.