.Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.ParallelFanCVF.Subsequences.ActiveAirFlow

Output the active primary airflow setpoint for constant-volume parallel fan-powered terminal unit

Information

This sequence sets the active primary cooling maximum and minimum setpoints for parallel fan-powered terminal unit with constant volume fan. The implementation is according to the Section 5.7.4 of ASHRAE Guideline 36, May 2020.

The setpoints shall vary depending on the mode of the zone group.

Setpoint Occupied Cooldown Setup Warm-up Setback Unoccupied
Cooling maximum (VActCooMax_flow) VCooMax_flow VCooMax_flow VCooMax_flow 0 0 0
Minimum (VActMin_flow) VOccMin_flow 0 0 0 0 0

Revisions


Generated at 2026-04-14T18:18:34Z by OpenModelicaOpenModelica 1.26.3 using GenerateDoc.mos