This package contains subsequences for controlling parallel fan-powered terminal unit with constant-volume fan. They are created according to Section 5.7 of ASHRAE Guideline 36, May 2020.
| Name | Description |
|---|---|
| ActiveAirFlow | Output the active primary airflow setpoint for constant-volume parallel fan-powered terminal unit |
| Alarms | Generate alarms of parallel fan-powered terminal unit with constant-volume fan |
| DamperValves | Output signals for controlling constant-volume parallel fan-powered terminal unit |
| Overrides | Software switches to override setpoints |
| SystemRequests | Output system requests for parallel fan-powered terminal unit with constant-volume fan |
| Validation | Collection of validation models |