This block considers the overrides to the setpoints for parallel fan-powered unit with constant-volume fan. The implementation is according to the Section 5.7.7 of ASHRAE Guideline 36, May 2020.
Provide software switches that interlock to a system-level point to:
oveDamPos
equals to 1, force the damper to full closed by setting
yDam
to 0,
oveDamPos
equals to 2, force the damper to full open by setting
yDam
to 1.
uHeaOff
equals to true
, force the heating valve to
full closed by setting yVal
to 0.
oveFan
equals to 1, force the fan to turn OFF.
oveFan
equals to 2, force the fan to turn ON.