This block considers the overrides to the setpoints for parallel fan-powered unit with constant-volume fan. The implementation is according to the Section 5.7.7 of ASHRAE Guideline 36, May 2020.
Provide software switches that interlock to a system-level point to:
oveDamPos equals to 1, force the damper to
full closed by setting yDam to 0,oveDamPos equals to 2, force the damper to
full open by setting yDam to 1.uHeaOff equals to true, force
the heating valve to full closed by setting yVal to
0.oveFan equals to 1, force the fan to turn
OFF.oveFan equals to 2, force the fan to turn
ON.