This sequence outputs the system reset requests for parallel fan-powered terminal unit with constant-voume fan. The implementation is according to the Section 5.7.8 of ASHRAE Guideline 36, May 2020.
yZonTemResReqTZon exceeds the zone
cooling setpoint TCooSet by 3 °C (5 °F)) for 2 minutes
and after suppression period (uAftSup=true) due to
setpoint change per G36 Part 5.1.20, send 3 requests
(yZonTemResReq=3).TZon exceeds the zone
cooling setpoint TCooSet by 2 °C (3 °F) for 2 minutes
and after suppression period (uAftSup=true) due to
setpoint change per G36 Part 5.1.20, send 2 requests
(yZonTemResReq=2).uCoo is greater than 95%,
send 1 request (yZonTemResReq=1) until
uCoo is less than 85%.uCoo is less than 95%, send 0 request
(yZonTemResReq=0).yZonPreResReqVPri_flow is less than 50%
of setpoint VSet_flow while the setpoint is greater
than zero and the damper position uDam is greater than
95% for 1 minute, send 3 requests
(yZonPreResReq=3).VPri_flow is less
than 70% of setpoint VSet_flow while the setpoint is
greater than zero and the damper position uDam is
greater than 95% for 1 minute, send 2 requests
(yZonPreResReq=2).uDam is greater than
95%, send 1 request (yZonPreResReq=1) until
uDam is less than 85%.uDam is less than 95%,
send 0 request (yZonPreResReq=0).yHeaValResReqTDis is 17 °C
(30 °F) thrTDis_1 less than the setpoint
TDisSet for 5 minutes, send 3 requests.TDis is 8
°C (15 °F) thrTDis_1 less than the setpoint
TDisSet for 5 minutes, send 2 requests.uVal is
greater than 95%, send 1 request until the hot water valve position
is less than 85%.uVal is less
than 95%, send 0 request.uVal is greater
than 95%, send 1 request until the hot water valve position is less
than 10%.uVal is less than
95%, send 0 requests.