This sequence outputs the system reset requests for parallel fan-powered terminal unit with constant-voume fan. The implementation is according to the Section 5.7.8 of ASHRAE Guideline 36, May 2020.
yZonTemResReq
TZon
exceeds the zone cooling setpoint
TCooSet
by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSup=true
) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonTemResReq=3
).
TZon
exceeds the zone cooling setpoint
TCooSet
by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSup=true
) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonTemResReq=2
).
uCoo
is greater than 95%, send 1 request
(yZonTemResReq=1
) until uCoo
is less than 85%.
uCoo
is less than 95%, send 0 request (yZonTemResReq=0
).
yZonPreResReq
VPri_flow
is less than 50% of setpoint
VSet_flow
while the setpoint is greater than zero and the damper position
uDam
is greater than 95% for 1 minute, send 3 requests (yZonPreResReq=3
).
VPri_flow
is less than 70% of setpoint
VSet_flow
while the setpoint is greater than zero and the damper position
uDam
is greater than 95% for 1 minute, send 2 requests (yZonPreResReq=2
).
uDam
is greater than 95%, send 1 request
(yZonPreResReq=1
) until uDam
is less than 85%.
uDam
is less than 95%, send 0 request
(yZonPreResReq=0
).
yHeaValResReq
TDis
is 17 °C (30 °F)
thrTDis_1
less than the setpoint TDisSet
for 5 minutes, send 3 requests.
TDis
is 8 °C (15 °F)
thrTDis_1
less than the setpoint TDisSet
for 5 minutes, send 2 requests.
uVal
is greater than 95%, send 1
request until the hot water valve position is less than 85%.
uVal
is less than 95%, send 0 request.
uVal
is greater than 95%, send 1
request until the hot water valve position is less than 10%.
uVal
is less than 95%, send 0 requests.