This sequence outputs the system reset requests for parallel fan-powered terminal unit with constant-voume fan. The implementation is according to the Section 5.7.8 of ASHRAE Guideline 36, May 2020.
yZonTemResReqTZon exceeds the zone cooling setpoint
TCooSet by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSup=true) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonTemResReq=3).
TZon exceeds the zone cooling setpoint
TCooSet by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSup=true) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonTemResReq=2).
uCoo is greater than 95%, send 1 request
(yZonTemResReq=1) until uCoo is less than 85%.
uCoo is less than 95%, send 0 request (yZonTemResReq=0).
yZonPreResReqVPri_flow is less than 50% of setpoint
VSet_flow while the setpoint is greater than zero and the damper position
uDam is greater than 95% for 1 minute, send 3 requests (yZonPreResReq=3).
VPri_flow is less than 70% of setpoint
VSet_flow while the setpoint is greater than zero and the damper position
uDam is greater than 95% for 1 minute, send 2 requests (yZonPreResReq=2).
uDam is greater than 95%, send 1 request
(yZonPreResReq=1) until uDam is less than 85%.
uDam is less than 95%, send 0 request
(yZonPreResReq=0).
yHeaValResReqTDis is 17 °C (30 °F)
thrTDis_1 less than the setpoint TDisSet
for 5 minutes, send 3 requests.
TDis is 8 °C (15 °F)
thrTDis_1 less than the setpoint TDisSet
for 5 minutes, send 2 requests.
uVal is greater than 95%, send 1
request until the hot water valve position is less than 85%.
uVal is less than 95%, send 0 request.
uVal is greater than 95%, send 1
request until the hot water valve position is less than 10%.
uVal is less than 95%, send 0 requests.