modelAlarms

Validation of model that generates alarms

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.ParallelFanCVF.Subsequences.Alarms for generating system alarms.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.ParallelFanCVF.Subsequences.AlarmsalaBlock outputs system alarms
Buildings.Controls.OBC.CDL.Reals.Sources.RampdisAirSetDischarge airflow rate setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.RampdisAirDischarge airflow rate
Buildings.Controls.OBC.CDL.Reals.Sources.RampdamPosDamper position
Buildings.Controls.OBC.CDL.Logical.Sources.PulsesupFanAHU supply fan status
Buildings.Controls.OBC.CDL.Conversions.BooleanToRealbooToReaConvert boolean input to real output
Buildings.Controls.OBC.CDL.Reals.MultiplymulDamper position
Buildings.Controls.OBC.CDL.Logical.Sources.PulsedamStaDamper open and close status
Buildings.Controls.OBC.CDL.Logical.Sources.PulsehotPlaHot water plant status
Buildings.Controls.OBC.CDL.Reals.Sources.RampTDisDischarge air temperature
Buildings.Controls.OBC.CDL.Logical.Sources.PulseterFanComOnTerminal fan command on status
Buildings.Controls.OBC.CDL.Logical.Sources.PulseterFanOnTerminal fan status
Buildings.Controls.OBC.CDL.Reals.Sources.RampvalPosValve position
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTSupAHU supply air temperature
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTDisSetDischarge airflow temperature setpoint
Buildings.Controls.OBC.CDL.Integers.Sources.PulseintPulOperation mode

Revisions

  • February 10, 2022, by Jianjun Hu:
    First implementation.