.Buildings.Examples.Tutorial.CDL.Controls.EquipmentOnOff

Information

Controller that takes as an input the boiler water temperature TBoi and the system on command onSys, and outputs the on command for the pumps onPum and the boiler onBoi.

The pump on command is the same as the system on command. The boiler is switched on if the boiler temperature TBoi falls below 70°C and if onSys=true, and it switches off if either TBoi exceeds 90°C or if onSys=false.