Controller for economizer
This is a controller for an economizer, that adjusts the mixed
air dampers to fulfill three control functions.
- Freeze protection, based on the mixed air temperature
measurement
- Minimum outside air requirement, based on the outdoor air flow
rate measurement
- Supply air cooling, based on the logic implemented in
Buildings.Examples.VAVReheat.BaseClasses.Controls.SupplyAirTemperature,
with the additional condition that when the outside air dry bulb is
greater than the return air dry bulb, economizer cooling is
disabled.
- August 31, 2021, by Michael Wetter:
Corrected selection of control signal during freeze
protection.
- October 27, 2020, by Antoine Gautier:
Refactored for compatibility with new supply air temperature
control.
This is for #2024.
- July 10, 2020, by Antoine Gautier:
Added optional reset signal. Corrected connections to
yOATFre.
This is for #2019
and #1995.
- December 20, 2016, by Michael Wetter:
Added type conversion for enumeration when used as an array
index.
This is for #602.
- April 26, 2016, by Michael Wetter:
Changed controller for freeze protection as the old implementation
closed the outdoor air damper during summer. This is for #511.