.Buildings.Examples.VAVReheat.BaseClasses.Controls.RoomVAV

Information

Controller for terminal VAV box with hot water reheat. It is based on the control logic "dual maximum with constant volume heating" as described in the Advanced VAV System Design Guide (EDR 2007). The controller could be used for units with the pressure independent damper and the units with the exponential damper, by setting the flag have_preIndDam.

Two separate control loops, the cooling loop and the heating loop, are implemented to maintain space temperature within a temperature dead band (with a required minimum width of 0.5 K). For the terminal boxes with the pressure independent damper, the damper control signal yDam corresponds to the discharge air flow rate set point, normalized to the nominal value. While for the boxes with the exponential damper, the damper position yDam is controlled by a PID loop to track the discharge airflow setpoint. The control signal for the reheat coil valve yVal corresponds to the fractional opening (1 corresponding to the valve fully open).

For the termnal boxes with the pressure independent damper (have_preIndDam=true),

For the termnal boxes with the exponential damper (have_preIndDam=false),

Note that a single maximum control logic can be represented by simply setting ratVFloHea equal to ratVFloMin (default setting).

image

References

EDR (Energy Design Resources). Advanced Variable Air Volume System Design Guide. Pacific Gas and Electric Company, 2007.


Revisions


Generated at 2024-12-28T19:26:00Z by OpenModelicaOpenModelica 1.24.3 using GenerateDoc.mos