This block computes the supply air temperature set point
based on the actual operating mode.
The default set point values are taken from the control sequence
VAV 2A2-21232 of the Sequences of Operation for
Common HVAC Systems (ASHRAE, 2006).
Operating mode | Set point value [C] |
---|---|
Occupied | 12 |
Unoccupied off | 12 |
Unoccupied, night set back | 35 |
Unoccupied, warm-up | 35 |
Unoccupied, pre-cool | 12 |
Safety | 7 |
ASHRAE. Sequences of Operation for Common HVAC Systems. ASHRAE, Atlanta, GA, 2006.