.Buildings.Examples.VAVReheat.BaseClasses.Controls.SupplyAirTemperatureSetpoint

Information

This block computes the supply air temperature set point based on the actual operating mode. The default set point values are taken from the control sequence VAV 2A2-21232 of the Sequences of Operation for Common HVAC Systems (ASHRAE, 2006).

Operating modeSet point value [C]
Occupied12
Unoccupied off12
Unoccupied, night set back35
Unoccupied, warm-up35
Unoccupied, pre-cool12
Safety7

References

ASHRAE. Sequences of Operation for Common HVAC Systems. ASHRAE, Atlanta, GA, 2006.