.Buildings.Examples.VAVReheat.BaseClasses.Guideline36

Information

This model consist of an HVAC system is a variable air volume (VAV) flow system with economizer and a heating and cooling coil in the air handler unit. There is also a reheat coil and an air damper in each of the five zone inlet branches.

See the model Buildings.Examples.VAVReheat.BaseClasses.PartialHVAC for a description of the HVAC system.

The control is based on ASHRAE Guideline 36, and implemented using the sequences from the library Buildings.Controls.OBC.ASHRAE.G36 for multi-zone VAV systems with economizer. The figures below shows the schematic diagram and controls of an HVAC system that supplies 5 zones:

image

A similar model but with a different control sequence can be found in Buildings.Examples.VAVReheat.ASHRAE2006. Note that this model, because of the frequent time sampling, has longer computing time than Buildings.Examples.VAVReheat.ASHRAE2006. The reason is that the time integrator cannot make large steps because it needs to set a time step each time the control samples its input.

Revisions


Generated at 2024-12-27T19:26:12Z by OpenModelicaOpenModelica 1.24.3 using GenerateDoc.mos