Partial model of variable air volume flow system with terminal
reheat that serves five thermal zones
This partial model consist of an HVAC system that serves
multiple thermal zones.
The HVAC system is a variable air volume (VAV) flow system with
economizer and a heating and cooling coil in the air handler unit.
There is also a reheat coil and an air damper in each of the zone
inlet branches. The figure below shows the schematic diagram of an
HVAC system that supplies 5 zones:

The control sequences for this HVAC system are added in the two
models that extend this model, namely Buildings.Examples.VAVReheat.ASHRAE2006
and Buildings.Examples.VAVReheat.Guideline36.
Contents
| Name |
Description |
MediumA |
Medium model for air |
MediumW |
Medium model for water |
- February 7, 2023, by Jianjun Hu:
Set the value of parameter transferHeat to
true for the mixed air temperature sensor.
- February 6, 2023, by Jianjun Hu:
Added junction to mix the return and outdoor air.
This is for issue
#3230.
- August 22, 2022, by Hongxiang Fu:
Replaced fan and pump models with preconfigured mover models. This
is for issue
#2668.
- April 26, 2022, by Michael Wetter:
Changed fan efficiency calculation to use Euler number.
This is for #2668.
- November 9, 2021, by Baptiste Ravache:
Vectorized the terminal boxes to be expanded to any number of
zones.
This is for issue
#2735.
- October 4, 2021, by Michael Wetter:
Refactored Buildings.Examples.VAVReheat
and its base classes to separate building from HVAC model.
This is for issue
#2652.
- September 3, 2021, by Michael Wetter:
Updated documentation.
This is for issue
#2600.
- August 24, 2021, by Michael Wetter:
Changed model to include the hydraulic configurations of the
cooling coil, heating coil and VAV terminal box.
This is for issue
#2594.
- June 30, 2021, by Antoine Gautier:
Changed cooling coil model. This is for issue
#2549.
- May 6, 2021, by David Blum:
Change to from_dp=false for all mixing box
dampers.
This is for issue
#2485.
- April 30, 2021, by Michael Wetter:
Reformulated replaceable class and introduced floor areas in base
class to avoid access of components that are not in the
constraining type.
This is for issue
#2471.
- April 16, 2021, by Michael Wetter:
Refactored model to implement the economizer dampers directly in
Buildings.Examples.VAVReheat.BaseClasses.PartialHVAC
rather than through the model of a mixing box. Since the version of
the Guideline 36 model has no exhaust air damper, this leads to
simpler equations.
This is for issue
#2454.
- March 11, 2021, by Michael Wetter:
Set parameter in weather data reader to avoid computation of wet
bulb temperature which is need needed for this model.
- February 03, 2021, by Baptiste Ravache:
Refactored the sizing of the heating coil in the
VAVBranch (renamed VAVReheatBox)
class.
This is for #2024.
- July 10, 2020, by Antoine Gautier:
Added design parameters for outdoor air flow.
This is for #2019
- November 25, 2019, by Milica Grahovac:
Declared the floor model as replaceable.
- September 26, 2017, by Michael Wetter:
Separated physical model from control to facilitate implementation
of alternate control sequences.
- May 19, 2016, by Michael Wetter:
Changed chilled water supply temperature to 6°C. This is for
#509.
- April 26, 2016, by Michael Wetter:
Changed controller for freeze protection as the old implementation
closed the outdoor air damper during summer. This is for #511.
- January 22, 2016, by Michael Wetter:
Corrected type declaration of pressure difference. This is for
#404.
- September 24, 2015 by Michael Wetter:
Set default temperature for medium to avoid conflicting start
values for alias variables of the temperature of the building and
the ambient air. This is for issue
426.
Generated at 2026-03-31T18:29:59Z by OpenModelicaOpenModelica 1.26.3 using
GenerateDoc.mos